Technical support – Delta VFD fault codes

    If a fault code appears on the drive display, use the tables below to identify the code and the recommended corrective action. If the fault persists or its cause is unclear, contact us for on-site diagnostics.

    Delta VFD-EL-W fault codes

    CodeFaultRecommended action
    ocOvercurrentCheck the wiring between the motor and drive for short circuits and verify the load. Increase the acceleration time.
    ovOvervoltageCheck the input voltage. Increase the deceleration time or use a braking resistor.
    oH1OverheatingCheck the ventilation openings and ambient temperature.
    LvLow voltageCheck the input voltage and phases.
    oLOverloadCheck the motor load. Use a higher-rated drive if necessary.
    oL1Electronic thermal overloadReduce the output current and check the settings.
    oL2Motor overloadReduce the motor load.
    EFExternal faultReset the drive after the external fault signal has cleared.
    ocAOvercurrent during accelerationIncrease the acceleration time and reduce torque compensation.
    ocdOvercurrent during decelerationIncrease the deceleration time.
    ocnOvercurrent at constant speedCheck the insulation and whether the motor is stalled.
    HLPhase lossCheck the incoming three-phase supply.
    cFAAutomatic acceleration/deceleration faultCheck the motor and regenerative energy.
    AErrAnalog signal faultCheck the ACI wiring.
    PTC1Internal motor overheatingCheck cooling, load and the rated-current setting.
    FbEPID feedback faultCheck parameter Pr.10.01 and the AVI/ACI wiring.
    dEvPID feedback deviationCheck the PID feedback wiring and parameters.
    HotPThermal fuse tripCheck the thermal load and parameter Pr.06.17.
    bbExternal base blockThe fault clears automatically after the BB signal is removed.
    cECommunication faultCheck the RJ45 wiring and communication protocol settings.
    cF1.0EEPROM write faultReturn the unit for service.
    cF2.0EEPROM read faultReset the drive; if the fault persists, return the unit for service.
    HPF1–HPF4Hardware faultReturn the unit for service.
    cF3.xWiring detection faultReturn the unit for service.

    Delta VFD-MS300 fault codes

    CodeFaultRecommended action
    ocAOvercurrent during accelerationIncrease the acceleration time and check the wiring.
    ocdOvercurrent during decelerationIncrease the deceleration time.
    ocnOvercurrent at constant speedCheck the insulation and whether the motor is stalled.
    GFGround faultCheck the insulation of the motor and cable.
    ocSOvercurrent during stopCheck the wiring.
    ov / ovd / ovn / ovSOvervoltageIncrease the deceleration time or use a braking resistor.
    LvA / Lvd / Lvn / LvSLow voltageCheck the input voltage and phases.
    OrPInput phase lossCheck the incoming three-phase supply.
    oH1IGBT overheatingCheck ventilation and ambient temperature.
    oLOverloadReduce the load or use a higher-rated drive.
    oL1 / EoL2Electronic thermal protectionCheck the motor-current setting.
    oH3Motor overheating (PTC/PT100)Check motor cooling and load.
    ot1 / ot2OvertorqueCheck the load and torque-detection settings.
    uCUnderloadCheck the motor wiring and load.
    cF2EEPROM read faultReset the drive; if the fault persists, service is required.
    AUEAuto-tuning faultCheck the motor data and wiring.
    EFExternal faultReset the drive after clearing the external fault signal.
    EF1Emergency stopReset the drive after clearing the emergency-stop signal.
    bbExternal base blockThe fault clears automatically after the BB signal is removed.
    STOSTO activeCheck the STO wiring and signal.
    STL1 / STL2 / STL3STO signal lossCheck the STO cable and connector.
    OPHLOutput phase lossCheck the motor wiring (U/V/W).
    CE1–CE10Communication faultCheck the Modbus wiring and protocol.

    Delta VFD-C2000plus fault codes

    CodeFaultRecommended action
    ocA / ocd / ocn / ocSOvercurrentCheck the wiring and increase the acceleration or deceleration time.
    GFGround faultCheck the insulation of the motor and cable.
    occIGBT short circuitService is required.
    ovA / ovd / ovn / ovSOvervoltageIncrease the deceleration time and use a braking resistor if necessary.
    LvA / Lvd / Lvn / LvSLow voltageCheck the input voltage.
    OrPInput phase lossCheck the three-phase supply.
    oH1IGBT overheatingCheck ventilation.
    oH2Internal component overheatingCheck ventilation and load.
    oL / EoL1 / EoL2OverloadReduce the load.
    oH3Motor overheatingCheck motor cooling.
    ot1 / ot2 / ot3 / ot4OvertorqueCheck the load.
    uCUnderloadCheck the motor wiring.
    AUE / AUE1–AUE5Auto-tuning faultCheck the motor data.
    EF / EF1External fault / Emergency stopReset the drive after clearing the signal.
    bbExternal base blockThe fault clears automatically.
    STO / STL1 / STL2 / STL3STO faultCheck the STO wiring.
    OPHLOutput phase loss (U/V/W)Check the motor wiring.
    CE1–CE10Modbus communication faultCheck the wiring and protocol.
    bFBrake transistor faultCheck the braking resistor.
    ydcStar-delta switching faultCheck the switching contactors.
    dEbDeceleration energy backup faultCheck the DC-bus voltage.

    On-site diagnostics and repair

    If the problem persists after identifying the fault code, or the cause is unclear, contact us for on-site diagnostics. We provide variable-frequency drive replacement, commissioning and on-site troubleshooting.